Which wire size should I use for a 12 V circuit?

Which wire size should I use for a 12 V circuit?
Size it for voltage drop, not current — at 12 V a small drop is a large percentage, so the cable is far thicker than the amps suggest.

The arithmetic is what surprises people. A 0.5 V drop on a 230 V circuit is negligible; the same 0.5 V on a 12 V circuit is over 4% and is enough to dim lights, slow a pump and make a winch behave as though its battery is flat. Because power is voltage times current, a 12 V circuit also carries roughly twenty times the current of a 230 V circuit doing the same work, and cable resistance loss rises with the square of that current. So 12 V wiring is thick, and its length matters enormously — a run to the back of a vehicle needs both directions counted. Fusing is the other half: every circuit is fused as close to the battery as practical, because it is the cable that is being protected, not the device.

The options, ranked

Ranked best-first for the stated job. The third column is why the others exist.
Option Good at Bad at
Stranded automotive cable (GXL/TXL or thin-wall) Flexible, and its insulation resists heat, oil and abrasion in a way household cable does not. Sized in different systems on either side of the Atlantic, so check what you are buying.
Crimped terminals A properly crimped joint is gas-tight and survives vibration; it is the automotive and aviation standard. Requires a decent ratchet crimper — pliers produce joints that fail later.
Soldered joints Excellent electrical contact. Solder wicks up the strands and creates a stiff point that fatigues and breaks under vibration.
Solid household cable Cheap and available. Work-hardens and fractures under vibration, and its insulation is not rated for engine bay heat or fuel.

Technique that changes the outcome

  1. Calculate total circuit length, counting both the positive and the return path
  2. Aim for under about 3% voltage drop, and less on anything motorised
  3. Fuse at the battery end, sized to the cable rather than to the appliance
  4. Crimp with a ratchet crimper and use adhesive-lined heatshrink where damp can reach
  5. Protect every point where the loom passes through metal with a grommet

What goes wrong

  • Sizing from current alone
  • Solid household cable in a vehicle
  • Unfused connections directly to a battery, which are a straightforward fire risk

Compiled practical guidance rather than a published standard. Product formulations vary by brand and market, so read the label — and where the work is structural, electrical or gas, the regulations that apply where you are govern rather than anything here.

Other cable and wire questions

For Use
Extension leads One with a conductor rated for the full load, and always fully unwound — a coiled cable reel can be derated to a fraction of its rating.
A socket circuit Typically 2.5 mm² for a UK ring final on a 32 A device, or 12 AWG on a US 20 A branch circuit — subject to the code and the installation method.
A lighting circuit Typically 1.0 or 1.5 mm² twin and earth in the UK, or 14 AWG on a 15 A circuit in the US — but the code and the installation method decide.
Outdoor and buried runs Steel wire armoured cable, or a direct-burial type, at the required depth with RCD or GFCI protection — never ordinary indoor cable.
An electric shower Commonly 6 or 10 mm² depending on the shower rating, the run length and the installation method — and it is notifiable work in most jurisdictions.
Speakers 16 AWG for short runs and 14 AWG beyond about 15 metres or into low-impedance speakers — and make sure it is copper, not copper-clad aluminium.

Common questions

Which wire size should I use for a 12 V circuit?
Size it for voltage drop, not current — at 12 V a small drop is a large percentage, so the cable is far thicker than the amps suggest.
What should I avoid?
Sizing from current alone Solid household cable in a vehicle Unfused connections directly to a battery, which are a straightforward fire risk